MODEL | FP 600 | FP 800 | FP 1K | FP 1.5K | FP 2K |
PHASE | Single phase |
CAPACITY | 600VA / 360W | 800VA / 480W | 1000VA / 600W | 1500VA / 900W | 2000VA / 1200W |
PARALLEL CAPABILITY | NO | | |
INPUT |
Nominal Voltage | 110 / 120Vac or 220 / 230 / 240Vac |
Voltage Range | 81-145Vac / 162-290Vac |
Frequency Range | 60 / 50Hz (auto sensing) |
Power Factor | - |
OUTPUT |
Output Voltage | 110 / 120Vac or 220 / 230 / 240Vac |
AC Voltage Regulation (Batt. Mode) | ± 10% |
Frequency Range (Synchronized Range) | - |
Frequency Range (Batt. Mode) | 60Hz or 50Hz ±1 Hz |
Current Crest Ratio | - |
Harmonic Distortion | - |
Transfer time AC mode to Battery mode | Typical 2-6 ms |
Transfer time Inverter to Bypass | - |
Waveform (Batt. Mode) | Simulated Sine Wave |
Overload AC Mode | - |
Overload Battery Mode | - |
EFFICIENCY |
AC Mode | - | - | - | - | - |
ECO Mode | - | - | - | - | - |
Battery Mode | - | - | - | - | - |
BATTERY |
Battery Type | 12V / 7Ah | 12V / 9Ah | 12V / 7Ah | 12V / 9Ah | 12V / 9Ah |
Numbers | 1 | 1 | 2 | 2 | 2 |
Typical Recharge Time | 4 hours recover to 90% capacity | 4-6 hours recover to 90% capacity |
INDICATORS |
AC mode | Green lighting | Green lighting |
Battery mode | Green flashing | Yellow flashing |
Fault | - | Red lighting |
ALARM |
Battery mode | Sounding every 10 seconds |
Low battery | Sounding every second |
Overload | Sounding every 0.5 second |
Fault | Continuosly sounding |
PROTECTION |
Full Protection | Overload, discharge and overcharge protection |
PHYSICAL |
Dimension, D X W X H (mm) | 279 x 101 x 142 | 320 x 130 x 182 |
Net Weight (kgs) | 4.25Kg | 4.9Kg | 8.2Kg | 10.4 Kg | 11 Kg |
ENVIRONMENT |
Operation Temperture | 0-40°C |
Operation Humidity | 0 - 90 % and non-condersing |
Noise Level | Less than 40dB @ 1 meter |
MANAGEMENT |
Smart RS-232/USB | - |
Optional SNMP | - |
Product specifications are subject to change without further notice |